Skip to content
York Gas Furnace Installation Manual
1. What are the Installation Requirements for a York Gas Furnace in a Residential Garage?
Clearances and Location:
- The furnace must be installed so that the burners and ignition source are at least 18 inches (46 cm) above the floor to prevent fire hazards and ensure proper ventilation.
- The furnace must be located or protected to avoid physical damage by vehicles in the garage.
- A minimum of 24 inches (61 cm) of clearance between the front of the furnace and an adjacent wall or another appliance is recommended for servicing access.
Ventilation Needs:
- The furnace requires adequate combustion air. If the indoor air quality may be compromised, outdoor air must be used for combustion.
- The venting system must be properly sized, connected, and pitched according to the installation instructions. It must be compatible with the furnace model and local codes.
Local Code Compliance:
- The installation must comply with all national, local, and state codes, including building, electrical, and mechanical codes.
- The installation must also comply with regulations of the serving gas supplier.
2. What Safety Precautions are Needed for Connecting Gas Piping to a York Gas Furnace?

Types of Fittings:
- Use fittings and piping materials that are approved for gas service and comply with local codes and standards.
Pressure Testing Requirements:
- Perform a leak test on the gas piping system before connecting it to the furnace by pressurizing the system with an inert gas and checking for leaks.
- Follow the specific pressure test procedure outlined in the installation manual.
Leak Detection Methods:
- Visually inspect the gas piping system for any signs of leaks or damage before and after the pressure test.
- Apply a non-corrosive leak check solution (such as a soap solution) to the connections and observe for bubbles, which indicate leaks.
3. How Should the Gas Valve Switch be Configured During York Gas Furnace Installation?
Correct Settings:
- Ensure the gas valve is set for the correct gas type (natural gas or propane) as indicated on the furnace’s rating plate.
- For installations at high altitudes, adjust the gas manifold pressure according to the charts provided in the installation manual.
Necessary Adjustments:
- For installations above 4,500 feet, adjust the gas manifold pressure and reduce the furnace input rate as required by the National Fuel Gas Code.
- Ensure the gas regulator is set correctly according to the manufacturer’s instructions and local gas supplier requirements.
Implications of Incorrect Configurations:
- Incorrect configurations can lead to explosion hazards, fire risks, or carbon monoxide poisoning, and can also cause premature failure of the furnace components.
Reference:
- York Installation Manual
- York Furnace Installation Guidelines
- York Furnace Technical Manuals